Answer and Explanation
It was initially specified that the receptacle outlet to be located within 50 ft of the electrical service equipment.
As well, instead of the receptacle being required within 50 ft., it is now required within 25 ft. of the service. This was to accommodate the typical 25 ft. cord used by many service electricians.
The rules apply to indoor service locations other than one-and two-family dwellings. For these locations, at least one 125-volt, single-phase, 15- or 20-ampere receptacle outlet must be installed in an accessible location within 25 ft. of the indoor electrical service equipment. The receptacle must be within the same room or area as the actual service equipment.
Having a maintenance receptacle near the electrical service allows for testing, servicing and connection of portable electrical data acquisition equipment for analyzing the electrical system.